200-240V 20A Automatic Transfer Switch (ATS) / Local Metered PDU (Agency de-rated to 16A continuous)
Provides a redundant power option for critical networking equipment with a single input power cord
2 digit display reports output power consumption in amps
1U horizontal rack-mount form factor; 14.8 in. / 37.6 cm depth
10 outlets (8 C13, 2 C19)
Set of Plug-lock output power cable retention sleeves prevent accidental disconnection of connected devices
Set of two C20 inlets support connection to separate PRIMARY and SECONDARY power sources
Two 12-ft. / 3.6m C19 to C20 power cables included
ATS circuits normally maintain output sourced from the primary input cable; As primary input power fails or becomes unstable, the ATS will switch to maintain output sourced from the secondary input cable until power on the primary input is restored and stable
ATS configurations enable fault-tolerant, hot-swappable UPS protection when used with a single UPS and fully redundant UPS protection when each cord is connected to a separate UPS system (in a two-UPS environment, the primary input cable must be supported by an online UPS with zero transfer time similar to SmartOnline series)
Advanced ATS configurations utilizing separate mains circuits, backup generators and even separate out of phase utility power grid feeds are fully supported
On-board ATS processor constantly evaluates power quality on both inputs to prevent transfer to the secondary source when unavailable or of lower quality than the primary source
Super-fast switchover between primary and secondary power sources occurs in 2-5 milliseconds
Built-in card slot supports optional SNMPWEBCARD or WEBCARDLX for permanent upgrade to a switched & monitored PDU system
Outlets are factory programmed for sequential turn-on at 250 millisecond intervals when the PDU is first energized to prevent inrush-related equipment interaction on startup
Front panel LEDs confirm power availability on both input lines
Federal Trade Agreements Act / TAA Compliant for GSA Schedule purchases
Design
Certification UL 60950 (USA, Canada), CE (Europe), Class A (Emissions), NOM (Mexico)
Country of origin Taiwan
Housing material Metal
LED indicators Y
Mounting Horizontal
PDU types Metered
Product colour Black
Features
Cable length 3.6 m
Rack capacity 1U
Logistics data
Products per master (outer) case 1 pc(s)
Operational conditions
Operating altitude 0 - 3000 m
Storage temperature (T-T) -15 - 50 °C
Other features
Dimensions (WxDxH) 439 x 376 x 44 mm
Ports & interfaces
Power plug C20 coupler
Power
AC input frequency 50 - 60 Hz
AC outlet types C13 coupler, C19 coupler
AC outlets quantity 10 AC outlet(s)
Maximum current 20 A
Nominal input voltage 200-240 V
Nominal output voltage 200-240 V
Sustainability
Sustainability certificates RoHS
Weight & dimensions
Depth 375.2 mm
Height 43.7 mm
Package depth 589.3 mm
Package height 137.2 mm
Package weight 8.07 kg
Package width 528.3 mm
Weight 4.69 kg
Width 440.2 mm

Write a review

Please login or register to review

Tripp Lite PDUMH20HVAT 3.8kW Single-Phase Local Metered Automatic Transfer Switch PDU, Two 200-240V C20 Inlets, 8 C13 & 2 C19 Outputs, 1U, TAA

  • Brand: Tripp-Lite
  • Product Code: PDUMH20HVAT
  • Availability: In Stock
  • $433.20


Specs: Icecat
The information published by Icecat is based on sources that can be considered reliable, but Icecat and its suppliers provide this information "AS IS" and do not guarantee correctness or completeness. The published information is only indicative and can be changed at any time without notification.